Official Distributor
SKU
MPN
RFC 4072S
Weight
3.257 kg
This product is Not Cancellable/Not Returnable
Series RFC
RFC 4072S - Safety controller
PLCnext Control with 4 x 10/100/1000 Ethernet, PROFINET controller with integrated PROFIsafe safety controller, PROFINET device, IP20 degree of protection, pluggable parameterization memory
- Integrated PROFINET controller and PROFINET device
- Support for PROFIsafe Profile V2.6.1
- System networking M2M with OPC UA
- Safety: highest level of safety of machinery, thanks to diversified processors and the support of up to 300 PROFIsafe devices
- PLCnext Technology for preferred programming languages and programming environments, open-source software, apps, PROFICLOUD, and soon, also PLCnext Store with real-time execution
- Performance: Use of one IntelR Core™ i5 dual-core processor and two powerful processors based on Arm architecture enables one of the best performance capabilities on the market
- Cybersecurity in accordance with IEC 62443
Technical Specifications
Product properties
Product family | PLCnext Control |
Type | Stand-Alone |
Insulation characteristics
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Pollution degree | 2 (when installed in a control cabinet or housing with IP54 degree of protection or higher) |
Display
Diagnostics display | yes |
System properties
Processor | Intel® Core™ i5-6300U 2x 2.4 GHz (Standard) |
Processor | Arm® Cortex®-A9, 800 MHz (CPU1) |
Processor | Arm® Cortex®-A8, 600 MHz (CPU2) |
Trusted Platform Module | TPM 1.2 |
Retentive data storage | 2 Mbyte |
IEC 61131 runtime system
Program Memory | 16 Mbyte |
Data storage system | 32 Mbyte |
PROFINET
Device function | PROFINET controller, PROFINET device |
Update rate | min. 1 ms |
Conformance class | B |
Number of supported devices | max. 256 |
Supported functions | Topology detection |
Supported functions | Automatic device replacement |
Supported functions | Parameterizable alarm and startup behavior |
Vendor ID | 00B0hex / 176dez |
Function
Diagnostics display | yes |
Controller redundancy | No |
Safety function | yes |
Functionality
Programming languages supported | Symbolic flowchart (SFC) |
Programming languages supported | Ladder diagram (LD) |
Programming languages supported | Function block diagram (FBD) |
Programming languages supported | Structured text (ST) |
Programming languages supported | C++ |
Programming languages supported | C# |
Programming languages supported | Java |
Programming languages supported | Python® |
Programming languages supported | Simulink® |
System requirements
Engineering tool | PLCnext Engineer |
Engineering tool | Eclipse® |
Engineering tool | Visual Studio® |
Engineering tool | MATLAB®/ Simulink® |
Application interface | OPC UA® |
Electrical properties
Power consumption | typ. 25 W (Without fan module) |
Power consumption | max. 35 W (With fan module) |
Maximum power dissipation for nominal condition | typ. 24 W (Without fan module) |
Maximum power dissipation for nominal condition | typ. 24 W (Without fan module) |
Supply
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including ripple (3.6 VPP)) |
Power supply connection | Screw terminal blocks, plug-in |
Typical current consumption | 1 A |
Real-time clock
Realtime Clock | integrated (capacitive buffering) |
Description realtime clock | 1.73 s/day = 20 ppm at 25 °C |
Connection data
Tightening torque | 0.5 ... 0.6 Nm |
COMBICON connector
Conductor cross section, rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Interfaces
Web server | yes |
USB
Number of interfaces | 1 |
Connection Method | USB type A, male connector |
Ethernet
Bus system | RJ45 |
Number of interfaces | 4 |
Connection Method | RJ45 jack |
Note on the connection method | Auto negotiation and auto crossing, auto polarity exchange |
Transmission Speed | 10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex) |
Transmission Speed | 10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex) |
External dimensions
Width / Height / Depth | 122 mm / 182 mm / 173 mm (without fan module) |
Width / Height / Depth | 122 mm / 220 mm / 173 mm (With fan module) |
Material specifications
Color | gray (RAL 7042) |
Safety data: EN ISO 13849
Category | max. 4 |
Performance level (PL) | max. e |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | max. 3 |
Safety data: EN IEC 62061
Safety Integrity Level Claim Limit (SIL CL) | max. 3 |
Ambient conditions
Degree of Protection | IP20 (Manufacturers declaration, not evaluated by UL) |
Ambient Temperature (Operation) | 0 °C ... 60 °C up to 2000 m above mean sea level (from 40 °C only with fan module) |
Ambient Temperature (Operation) | 0 °C ... 55 °C 2000 m ... 3000 m above mean sea level (With fan module only) |
Ambient Temperature (Operation) | 0 °C ... 50 °C 3000 m ... 4000 m above mean sea level (With fan module only) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Shock (operation) | 20g (in accordance with EN 60068-2-27/IEC 60068-2-27) |
Shock (storage/transport) | 20g (in accordance with EN 60068-2-27/IEC 60068-2-27) |
Vibration (Operation) | 1g (in accordance with EN 60068-2-6/IEC 60068-2-6) |
Vibration (storage/transport) | 1g (in accordance with EN 60068-2-6/IEC 60068-2-6) |
Air pressure (operation) | 60 kPa ... 108 kPa (up to 4000 m above mean sea level) |
Air pressure (storage/transport) | 58 kPa ... 108 kPa (up to 4500 m above mean sea level) |
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Use of the device in these ambient conditions is prohibited. |
EMC data
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge |
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion B, Supply lines: ±2 kV, Signal/data lines: ±2 kV |
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines: ±0.5 kV, signal/data cables: ±1 kV |
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V |
Conformance with EMC directives | Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 1051328?
Proax is an authorized distributor of Phoenix Contact 1051328 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |