CADEN
Cart

1072838

Official Distributor

By Phoenix Contact

SKU
PHX1072838
MPN
IOL MA8 PN DI8
Weight
0.373 kg
This product is Not Cancellable/Not Returnable
Series IOL-MA8

IOL MA8 PN DI8 - Communication module

Eight-channel IO-Link master provides convenient configuration of IO-Link devices using web-based management. Supports connectivity to PROFINET IO, MODBUS, and OPC UA. Features eight auxiliary digital inputs, redundant input power supply connections, plug-in push-in terminals.

  • Web-based management
  • Eight-channel IO-Link master
  • Diagnostic and status indicators
  • Short-circuit and overload protection of the sensor supply
  • Plug-in connection terminals, push-in connection technology
  • Connections for up to 16 digital sensors
Technical Specifications

Dimensions

Width45 mm
Height114.5 mm
Depth99 mm

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area

Material specifications

Housing MaterialPolyamide
Colorgray

PROFINET

No. of channels2
Connection MethodRJ45 jack
Transmission Speed10/100 Mbps (with auto negotiation)
Transmission physicsEthernet in RJ45 twisted pair
Equipment typePROFINET-Device
System-specific protocolsPROFINET protocols LLDP
System-specific protocolsPROFINET protocols MRP client
System-specific protocolsPROFINET protocols DCP
System-specific protocolsDCE/RPC
Protocols SupportedSNMP v1
Protocols SupportedHTTP
Protocols SupportedTFTP
Protocols SupportedFTP
Protocols SupportedBootP
Protocols SupportedDHCP
Protocols SupportedSSH

Digital:

Input nameDigital inputs
Description of the inputIEC 61131-2 type 1
Number of Inputs8
Connection MethodPush-in / plug connection
Connection technology3-conductor
Input voltage range "0" signal0 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 3.5 mA
Input Frequency0.5 kHz
Protective circuitOverload protection
Protective circuitShort-circuit protection for the sensor supply

Digital

Input nameDigital inputs
Description of the inputIO-Link ports in digital input (DI) mode
Number of Inputsmax. 8 (EN 61131-2 types 1 and 3)
Connection MethodPush-in / plug connection
Connection technology3-conductor
Nominal input voltage UIN24 V DC
Input voltage range "0" signal8 V DC ... 11.5 V DC (for C/Q pin)
Input voltage range "1" signal10.5 V DC ... 13 V DC
Sensor current per channelmax. 200 mA (from L+/L-)
Total sensor currentmax. 1.6 A (from L+/L-)
Protective circuitOverload protection; yes
Protective circuitShort-circuit protection for the sensor supply; electronic

IO-Link

Description of the inputDigital inputs (DI)
Connection MethodPush-in / plug connection
Nominal input voltage UIN24 V DC
Input voltage range "0" signal5.2 V DC ... 6.4 V DC
Input voltage range "1" signal6.8 V DC ... 8 V DC
Nominal input currenttyp. 3.5 mA
Sensor current per channelmax. 200 mA (from L+/L-)
Total sensor currentmax. 1.6 A (from L+/L-)
Protective circuitOverload protection; yes
Protective circuitShort-circuit protection for the sensor supply; yes
Number of Ports8
Connection MethodPush-in / plug connection
Connection technology3-conductor
Cycle Timemin. 4 ms (IO-Link cycle time)

Digital:

Maximum Output Current per channel200 mA

Digital

Output descriptionIO-Link ports in digital output (DO) mode
Connection MethodPush-in / plug connection
Connection technology3-conductor
Number of Outputsmax. 8
Nominal Output Voltage24 V DC
Maximum Output Current per channel200 mA
Maximum Output Current per module1.6 A
Nominal load, ohmic4.8 W (120 Ω, at nominal load)
Output voltage when switched offmax. 1 V
Output current when switched offmax. 400 µA
Protective circuitOverload protection
Protective circuitShort-circuit protection; yes
Behavior with overloadShutdown with automatic restart

Product properties

Product familyStand-Alone
TypeStand-Alone

Supply: IO-Link

Nominal voltage for I/O supply24 V DC
Nominal current for every IO-Link portmax. 200 mA (at C/Q)
Nominal current for every IO-Link portmax. 200 mA (at L+/L-)
Permissible cable length< 20 m
Protective circuitOverload protection; yes

Potentials

Supply Voltage24 V DC
Supply Voltage Range10.8 V DC ... 30 V DC
Current draw155 mA

Supply: Module electronics

Supply Voltage24 V DC
Supply Voltage Range18 V DC ... 30 V DC
Current consumption3.7 A

Supply:

Supply Voltage24 V DC
Supply Voltage Range18 V DC ... 30 V DC
Current consumptionmax. 3.7 A
Typical current consumption155 mA (at 24 V DC)

Electrical isolation/isolation of the voltage ranges

Test voltage: 24 V supply/Ethernet500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (US) / FE500 V AC, 50 Hz, 1 min.
Test voltage: Ethernet/FE500 V AC, 50 Hz, 1 min.
Test voltage: Ethernet/Ethernet500 V AC, 50 Hz, 1 min.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Stripping length10 mm
Connection MethodPush-in connection
Conductor cross section, rigid0.2 mm² ... 2.5 mm²
Conductor cross section, flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Stripping length10 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 %
Permissible humidity (storage/transport)10 % ... 95 %

Mounting

Mounting TypeDIN rail mounting

Why Proax for Phoenix Contact 1072838?

Proax is an authorized distributor of Phoenix Contact 1072838 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size1
Recommended

CAD$1,380.00

130 in stock at Phoenix Contact
Phoenix Contact USA
130
Phoenix Contact Availability