MPDB62190
By Mersen
SKU
MERMPDB62190
Weight
0.141 kg
Open-Style PDB UL 1953 1000V Tin‑plated Copper – 175A Adder, 1‑2 openings; 2/0‑#14 --- #2‑#14 Box to Box
Technical Specifications
| Rated Voltage Ac Ul | 1000 V |
| Rated Voltage Dc Ul | 1000 V |
| Frequency | 50/60 Hz |
| Number of Poles | Adder |
| Installation Mounting | Direct Screw Mount |
| Body Insulating Material | Glass Filled Polycarbonate |
| Ampere Rating Cu | 175 A |
| Connector Material | Tin‑plated Copper |
| short circuit rating class cc | 100 kA with 30 A Fuse |
| short circuit rating class g | 100 kA with 60 A Fuse |
| short circuit rating class j | 100 kA with 100 A Fuse |
| short circuit rating class l | 100 kA with 100 A Fuse |
| short circuit rating class rk1 | 100 kA with 60 A Fuse |
| short circuit rating class rk5 | 100 kA with 30 A Fuse |
| Short Circuit Rating Standalone | 10 kA |
| short circuit rating class t | 100 kA with 100 A Fuse |
| Number Of Openings Per Pole Primary | 1 |
| Number Of Openings Per Pole Secondary | 2 |
| Connector Type Primary | Box |
| Connector Type Secondary | Box |
| hex screw size type primary | 3/8‑24 × 0.56 in |
| hex screw size type secondary | 5/16‑24 × 0.38 in |
| hole diameter primary | 0.44 in |
| hole diameter secondary | 0.31 in |
| torque rating primary | 2/0‑#3 50; #4‑#6 45; #8 40; #10‑#14 35 in‑lb |
| torque rating secondary | #2‑#3 50; #4‑#6 35; #8 25; #10‑#14 20 in‑lb |
| Wire Range Primary | 2/0‑#14 |
| Wire Range Secondary | #2‑#14 |
| product dimensions w l h | 23.6 mm × 78.2 mm × 71.4 mm |
Why Proax for Mersen MPDB62190?
Proax is the authorized distributor of Mersen MPDB62190. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended