SMISSLINE TP S400M are a current limiting miniature circuit breakers. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K), configurations (1P,1P+N,2P,3P,3P+N), breaking capacities (up to 10 kA at 240/415 V AC ) and rated currents (up to 63A). MCBs of the product range S400M are comply with IEC/EN 60898-1 for B,C and D characteristic and IEC/EN 60947-2 for C and K characteristic. The pluggable solution is only for the SMISSLINE TP System, allowing the use for commercial, industrial, and critical power applications.
Technical Specifications

ABB EcoSolutions

ABB EcoSolutionsYes
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 92.73 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
Sustainable Material Content in Packaging (wt. %)Recycled Cardboard - 18.12 %
Sustainable Material Content in Packaging (wt. %)Recycled Cardboard - 67.66 %
Sustainable Material Content in Packaging (wt. %)Chemically Recycled Polymer - 0 %
Extended Product LifetimeProduct Durability
End Of Life Disassembling Instructions9AKK108469A6908
Environmental Product Declaration - EPD9AKK108469A5735

Technical

Rated Operational Current (Ie)4 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V) 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V) 25 kA
Rated Short-Circuit Making Capacity (Icm)(240 V AC) 52.5 kA
Rated Short-Circuit Making Capacity (Icm)(254 V AC) 30 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 15 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(254 V AC) 7.5 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)50 %
Power supply connectionArbitrary
Contact Position IndicationRed ON / Green OFF
Energy Limiting Class3
Electrical Endurance10000 cycle
Mechanical Endurance10000 cycle
Number of Protected Poles1
Number of Poles1P
Tightening torque2.8 N·m
Release TypeK
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Actuator MarkingI / O
Recommended Screw DriverPozidriv 2
Accessories AvailableYes
Connecting CapacityFlexible 0.75 … 25 mm²
Connecting CapacityRigid 0.75 … 35 mm²
Terminal TypeScrew Terminals

Electrical

Tripping characteristicK
Rated Operational Voltageacc. to IEC 60898-1 240 V
Operational VoltageMaximum (Incl. Tolerance) 254 V AC
Operational VoltageMinimum 12 V AC
Operational VoltageMinimum 12 V DC
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Input Voltage TypeAC
Rated Current (In)4 A
Rated Short-Circuit Capacity(230 V) 10 kA
Rated Short-Circuit Capacity(400 V) 10 kA
Frequency (f)50 ... 60 Hz
Rated Frequency (f)50 ... 60 Hz
Power Loss1.4 W
Overvoltage categoryIII

Dimensions

Width in Number of Modular Spacings1
Product Net Width18 mm
Product Net Height91 mm
Product Net Depth / Length75 mm
Product Net Weight110 g
Built-In Depth (t2)75 mm
Dimension Diagram9AKK107492A6192

Engineering

EPLAN Data9AAC128473_EPLAN

Installation

Instructions and Manuals2CCC451019M0109
Mounting PositionAny

Why Proax for ABB S401M-K4?

Proax is an authorized distributor of ABB S401M-K4 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesS401MK4
Pack Size1
Recommended

CAD$53.74

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability