The CM-ENS.13P belongs to the CM liquid level monitoring relay range. It operates with a rated control supply voltage of 110-130 V AC and 220-240 V AC and has a 1 c/o (SPDT) output with contacts rated at 250 V / 4 A. It monitors liquid levels of conductive fluids and protects pumps against dry running or tanks against overflow and works according to the open-circuit principle. The sensitivity can be selected via front-face potentiometers. Several electrodes and a sealable transparent cover for protection against unauthorized changes are available as accessory. The device offers maintenance free Easy Connect Technology with push-in terminals.
Technical Specifications
Dimensions
Product Net Width | 22.5 mm |
Product Net Height | 85.6 mm |
Product Net Depth / Length | 103.7 mm |
Product Net Weight | 0.145 kg |
Technical
Function | Filling or draining monitoring |
Number of Electrodes | 3 |
Measuring Range | 5 ... 100 kΩ |
Rated Control Supply Voltage (Us) | 110 ... 130 V AC |
Rated Control Supply Voltage (Us) | 220 ... 240 V AC |
Rated Frequency (f) | Supply Circuit 50/60 Hz |
Output | 1 c/o (SPDT) contact |
Terminal Type | Screwless Terminals |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
Minimum switching capacity | 12 V |
Minimum switching capacity | 10 mA |
Rated Impulse Withstand Voltage (Uimp) | Measuring Circuit / Output Circuit 4 kV |
Rated Impulse Withstand Voltage (Uimp) | Output Circuit 1 / Output Circuit 2 4 kV |
Rated Impulse Withstand Voltage (Uimp) | Supply Circuit / Measuring Circuit 4 kV |
Rated Impulse Withstand Voltage (Uimp) | Supply Circuit / Output Circuit 4 kV |
Rated Insulation Voltage (Ui) | Measuring Circuit / Output Circuit 300 V |
Rated Insulation Voltage (Ui) | Output Circuit 1 / Output Circuit 2 300 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Measuring Circuit 300 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Output Circuit 300 V |
Degree of Protection | Housing IP50 |
Degree of Protection | Terminals IP20 |
Overvoltage category | III |
Pollution degree | 3 |
Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 6 A |
Short-Circuit Protective Devices | Output Circuit NO - F Type Fuses 10 A |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 1000000 cycle |
Connecting Capacity | Flexible with Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Rigid 2x 0.5 ... 1.5 mm² |
Tightening torque | Control Circuit 0.9 N·m |
Tightening torque | Main Circuit 1 N·m |
Wire Stripping Length | 8 mm |
Wire Stripping Length | Main Circuit 10 mm |
Mounting Position | 1 ... 5 |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14 |
Standards | IEC/EN 63000 |
Standards | IEC/EN 60255-27 |
Standards | IEC/EN 61000-6-2 |
Standards | IEC/EN 61000-6-3 |
Standards | UL 508 |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
Contact Rating UL/CSA | B300 |
Connecting Capacity UL/CSA | Flexible 2x 18-16 AWG |
Connecting Capacity UL/CSA | Rigid 2x 20-16 AWG |
Pilot Duty UL/CSA | B300 |
Why Proax for ABB CM-ENS.13P?
Proax is an authorized distributor of ABB CM-ENS.13P and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | CMENS13P |
Pack Size | 1 |
Recommended