The AFS09-30-22-13 is a 3 pole - 690 V IEC or 600 V UL contactor with fixed 2 N.O + 2 N.C. front mounted auxiliary contact blocks with screw connections, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (100 ... 250 V), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical Specifications

Dimensions

Product Net Width45 mm
Product Net Depth / Length110.5 mm
Product Net Height86 mm
Product Net Weight0.32 kg

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Rated Frequency (f)Control Circuit 50 / 60 Hz
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 25 A
Rated Operational Current AC-1 (Ie)(690 V) 60 °C 25 A
Rated Operational Current AC-1 (Ie)(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 9 A
Rated Operational Current AC-3 (Ie)(440 V) 60 °C 9 A
Rated Operational Current AC-3 (Ie)(500 V) 60 °C 9.5 A
Rated Operational Current AC-3 (Ie)(690 V) 60 °C 7 A
Rated Operational Current AC-3 (Ie)(380 / 400 V) 60 °C 9 A
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)(440 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)(500 V) 60 °C 9.5 A
Rated Operational Current AC-3e (Ie)(690 V) 60 °C 7 A
Rated Operational Current AC-3e (Ie)(380 / 400 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Power AC-3 (Pe)(400 V) 4 kW
Rated Operational Power AC-3 (Pe)(415 V) 4 kW
Rated Operational Power AC-3 (Pe)(440 V) 4 kW
Rated Operational Power AC-3 (Pe)(500 V) 5.5 kW
Rated Operational Power AC-3 (Pe)(690 V) 5.5 kW
Rated Operational Power AC-3 (Pe)(380 / 400 V) 4 kW
Rated Operational Power AC-3 (Pe)(220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)(415 V) 4 kW
Rated Operational Power AC-3e (Pe)(440 V) 4 kW
Rated Operational Power AC-3e (Pe)(500 V) 5.5 kW
Rated Operational Power AC-3e (Pe)(690 V) 5.5 kW
Rated Operational Power AC-3e (Pe)(380 / 400 V) 4 kW
Rated Operational Power AC-3e (Pe)(220 / 230 / 240 V) 2.2 kW
Rated Operational Current AC-15 (Ie)(500 V) 2 A
Rated Operational Current AC-15 (Ie)(690 V) 2 A
Rated Operational Current AC-15 (Ie)(24 / 127 V) 6 A
Rated Operational Current AC-15 (Ie)(220 / 240 V) 4 A
Rated Operational Current AC-15 (Ie)(400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Rated Short-time Withstand Current Low Voltage (Icw)for 0.1 s 140 A
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour
Maximum Electrical Switching Frequency(AC-2 / AC-4) 300 cycles per hour
Maximum Electrical Switching Frequency(AC-3) 1200 cycles per hour
Maximum Electrical Switching Frequency(DC-13) 900 cycles per hour
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 40 °C 10 A
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 60 °C 10 A
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 70 °C 10 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 70 °C 22 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-1 (Ie)(220 V) 2 Poles in Series, 40 °C 10 A
Rated Operational Current DC-1 (Ie)(220 V) 2 Poles in Series, 60 °C 10 A
Rated Operational Current DC-1 (Ie)(220 V) 2 Poles in Series, 70 °C 10 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 70 °C 22 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 70 °C 22 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 40 °C 6 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 60 °C 6 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 70 °C 6 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(220 V) 2 Poles in Series, 40 °C 6 A
Rated Operational Current DC-3 (Ie)(220 V) 2 Poles in Series, 60 °C 6 A
Rated Operational Current DC-3 (Ie)(220 V) 2 Poles in Series, 70 °C 6 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(72 V) 1-Pole, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 1-Pole, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 1-Pole, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 40 °C 4 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 60 °C 4 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 70 °C 4 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 10 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 60 °C 10 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 70 °C 10 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)(220 V) 2 Poles in Series, 40 °C 4 A
Rated Operational Current DC-5 (Ie)(220 V) 2 Poles in Series, 60 °C 4 A
Rated Operational Current DC-5 (Ie)(220 V) 2 Poles in Series, 70 °C 4 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 40 °C 9 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 60 °C 9 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 70 °C 9 A
Rated Operational Current DC-5 (Ie)(72 V) 1-Pole, 40 °C 9 A
Rated Operational Current DC-5 (Ie)(72 V) 1-Pole, 60 °C 9 A
Rated Operational Current DC-5 (Ie)(72 V) 1-Pole, 70 °C 9 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 40 °C 25 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 60 °C 25 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 40 °C 25 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 60 °C 25 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
Rated Operational Current DC-13 (Ie)(48 V) 2.8 A / 134 W
Rated Operational Current DC-13 (Ie)(72 V) 1 A / 72 W
Rated Operational Current DC-13 (Ie)(110 V) 0.55 A / 60 W
Rated Operational Current DC-13 (Ie)(125 V) 0.55 A / 69 W
Rated Operational Current DC-13 (Ie)(220 V) 0.27 A / 60 W
Rated Operational Current DC-13 (Ie)(250 V) 0.27 A / 68 W
Rated Operational Current DC-13 (Ie)(400 V) 0.15 A / 60 W
Rated Operational Current DC-13 (Ie)(500 V) 0.13 A / 65 W
Rated Operational Current DC-13 (Ie)(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
Rated Insulation Voltage (Ui)acc. to IEC 60947-5-1 690 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V
Rated Control Circuit Voltage (Uc)60 Hz 100 ... 250 V
Rated Control Circuit Voltage (Uc)DC Operation 100 ... 250 V
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Operate TimeBetween Coil De-energization and NO Contact Opening 11 ... 95 ms
Operate TimeBetween Coil Energization and NC Contact Opening 38 ... 90 ms
Operate TimeBetween Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 screws placed diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Connecting Capacity Main CircuitFlexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Main CircuitRigid Solid 1/2x 1 ... 4 mm²
Connecting Capacity Main CircuitRigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitRigid Solid 1/2x 1 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitRigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Connecting Capacity Control CircuitRigid Solid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitRigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Wire Stripping LengthControl Circuit 10 mm
Wire Stripping LengthMain Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal TypeScrew Terminals

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 25 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 3/4 hp
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 2 hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 2 hp
Horsepower Rating UL/CSA(240 V AC) Single Phase 1-1/2 hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 5 hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 7-1/2 hp
Connecting Capacity Main Circuit UL/CSARigid Solid 1/2x 16-10 AWG
Connecting Capacity Main Circuit UL/CSARigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Connecting Capacity Auxiliary Circuit UL/CSARigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSARigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb
Tightening Torque UL/CSAControl Circuit 11 in·lb
Tightening Torque UL/CSAMain Circuit 13 in·lb

Why Proax for ABB AFS09-30-22-13?

Proax is an authorized distributor of ABB AFS09-30-22-13 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAFS09302213
Pack Size1