By ABB
SKU
MPN
2CCS862001R1105
Weight
0.508 kg
S802S-UCB10 High Performance Miniature Circuit Breaker 2 Poles B Characteristic 10A 50kA 250VDC
Spécifications techniques
Technique
Normes et standards | IEC/EN 60947-2 |
Tripping Characteristic | UC-B |
Type of Residual Current | standard version |
Tension nominale (Ur) | acc. to IEC 60947-2 500 V DC |
Tension | acc. to IEC 60947-2 500 V DC |
Tension assignée d’isolement (Ui) | acc. to IEC/EN 60664-1 1000 V |
Tension assignée de tenue aux chocs (Uimp) | 8 kV |
Type de tension | DC |
Courant nominal (IN) | 10 A |
Courant nominal de fonctionnement (Ie) | 10 A |
Pouvoir assigné de coupure ultime en court-circuit (Icu) | (500 V DC) 50 kA, (230 V) 50 kA, (400 V) 50 kA |
Rated Conditional Short-Circuit Current (Inc) | (230 V) 50 kA, (400 V) 50 kA |
Pourvoir assigné de coupure de service en court-circuit (Ics) | (500 V DC) 50 kA |
Fréquence (f) | 50...60 Hz |
Fréquence assignée (f) | 50 ... 60 Hz |
Power Loss | 3 W, at Rated Operating Conditions per Pole 1.5 W |
Contact Position Indication | ON / OFF / TRIP |
Classe de limitation d'énergie | 3 |
Nombre de pôles | 2 |
Number of Protected Poles | 2 |
Catégorie de surtension | III |
Type de libération | b |
Actuator Marking | I / O |
Accessories Available | Oui |
Connecting Capacity | Flexible 0...50 mm², Rigid 0...70 mm² |
Type de borne | Bornes à vis |
Environnement
Température extérieure | -25...60 °C |
Température de l’air ambiant | Operation -25...60 °C |
Indice de protection | IP20 |
Degré de pollution | 2 |
Statut RoHS | Following EU Directive 2011/65/EU |
Dimensions
Width in Number of Modular Spacings | 3 |
Produit Largeur Net | 54 mm |
Produit Hauteur Net | 95 mm |
Produit Longueur Net | 82,5 mm |
Poids net | 490 g |
Taille | 2 modules |
Profondeur d'encastrement (t2) | 82,5 mm |
Pourquoi Proax pour ABB S802S-UCB10?
Proax est un distributeur autorisé de ABB S802S-UCB10 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
Autres noms | S802SUCB10 |
Taille de l'emballage | 1 |
Recommandé
- The S802S-UCB10-R is a 1-pole High Performance Circuit breaker for DC application with B-characteristic, with ring tongue terminal and a rated current of 10 A. It is a current limiting device with a maximum breaking capacity of 50kA at 500V. It can be used for voltages up to 500V DC. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-UCB10-R complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-UCB10-R more comfortable. Due to the fast arc extinction of S802S-UCB10-R your application will be secured.
- The S802S-UCB13-R is a 1-pole High Performance Circuit breaker for DC application with B-characteristic, with ring tongue terminal and a rated current of 13 A. It is a current limiting device with a maximum breaking capacity of 50kA at 500V. It can be used for voltages up to 500V DC. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-UCB13-R complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-UCB13-R more comfortable. Due to the fast arc extinction of S802S-UCB13-R your application will be secured.
- The S802S-UCK25-R is a 1-pole High Performance Circuit breaker for DC application with K-characteristic, with ring tongue terminal and a rated current of 25 A. It is a current limiting device with a maximum breaking capacity of 50kA at 500V. It can be used for voltages up to 500V DC. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-UCK25-R complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-UCK25-R more comfortable. Due to the fast arc extinction of S802S-UCK25-R your application will be secured.