By ABB
SKU
MPN
1SFL637081R7112
Weight
1 kg
The AFS750-30-12-71 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Spécifications techniques
Dimensions
Produit Largeur Net | 210 mm |
Produit Longueur Net | 242 mm |
Produit Hauteur Net | 283 mm |
Poids net | 10 kg |
Technique
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 |
Number of Auxiliary Contacts NC | 2 |
Tension | Circuit principal 1000 V |
Fréquence assignée (f) | Circuit principal 50 / 60 Hz |
Courant thermique conventionnel à l’air libre (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1050 A |
Courant assignée d’emploi AC-1 (Ie) | (1000 V) 40 °C 1000 A, (1000 V) 55 °C 875 A, (1000 V) 70 °C 720 A, (690 V) 40 °C 1050 A, (690 V) 55 °C 875 A, (690 V) 70 °C 720 A |
Courant assignée d’emploi AC-3 (Ie) | (415 V) 55 °C 750 A, (440 V) 55 °C 750 A, (500 V) 55 °C 750 A, (690 V) 55 °C 650 A, (1000 V) 55 °C 300 A, (380 / 400 V) 55 °C 750 A, (220 / 230 / 240 V) 55 °C 750 |
Puissance assignée d’emploi AC-3 (Pe) | (415 V) 425 kW, (440 V) 450 kW, (500 V) 520 kW, (690 V) 600 kW, (1000 V) 400 kW, (380 / 400 V) 400 kW, (220 / 230 / 240 V) 220 kW |
Pouvoir assigné de coupure AC-3 | 8 x Ie AC-3 |
Pouvoir assigné de fermeture AC-3 | 10 x Ie AC-3 |
Dispositif de protection contre les courts-circuits | gG Type Fuses 1000 A |
Courant assigné de courte durée admissible (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3500 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 7000 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4500 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-2 / AC-4) 60 cycles per hour, (AC-3) 300 cycles per hour |
Courant assignée d’emploi DC-1 (Ie) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A, (850 V) 3 Poles in Series, 40 °C 1050 A |
Courant assignée d’emploi DC-3 (Ie) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A, (850 V) 3 Poles in Series, 40 °C 1050 A |
Courant assignée d’emploi DC-5 (Ie) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A, (850 V) 3 Poles in Series, 40 °C 1050 A |
Tension assignée d’isolement (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
Tension assignée de tenue aux chocs (Uimp) | Circuit principal 8 kV |
Durabilite mecanique | 5 million |
Maximum Mechanical Switching Frequency | 300 cycles per hour |
Plage d'utilisation de la bobine selon | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc) | 50 Hz 250 ... 500 V, 60 Hz 250 ... 500 V, DC Operation 250 ... 500 V |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A, Holding at Max. Rated Control Circuit Voltage DC 5.5 V·A, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 985 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 985 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 910 V·A |
Durée de fonctionnement nominale | Entre la mise hors tension de la bobine et la fermeture du contact NC (normally closed) 50 ... 70 ms, Entre la mise hors tension de la bobine et l'ouverture du contact NO (normally open) 53 ... 73 ms, Entre la mise sous tension de la bobine et l'ouverture du contact NC 45 ... 115 ms, Entre la mise sous tension de la bobine et la fermeture du contact NO 50 ... 120 ms |
Connecting Capacity Main Circuit | Bar 52 mm², Rigid Al-Cable 300 mm², Rigid Cu-Cable 300 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Flexible 1x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm² |
Indice de protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Type de borne | Main Circuit: Bars |
Technique UL/CSA
NEMA Size | 7 |
Horsepower Rating NEMA | (230 V AC) Three Phase 300 Hp, (460 V AC) Three Phase 600 Hp, (575 V AC) Three Phase 600 Hp |
Maximum Operating Voltage UL/CSA | Circuit principal 600 V |
General Use Rating UL/CSA | (1000 V AC) 900 A, (600 V AC) 900 A |
Puissance nominale UL/CSA | (200 ... 208 V AC) Three Phase 250 hp, (220 ... 240 V AC) Three Phase 300 hp, (440 ... 480 V AC) Three Phase 600 hp, (550 ... 600 V AC) Three Phase 700 hp |
Environnement
Température de l’air ambiant | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C, Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C, Close to Contactor for Storage -40 ... +70 °C |
Altitude de fonctionnement maximale autorisée | Without Derating 3000 m |
Statut RoHS | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Pourquoi Proax pour ABB AFS750-30-12-71?
Proax est un distributeur autorisé de ABB AFS750-30-12-71 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
Autres noms | AFS750301271 |
Taille de l'emballage | 1 |
Recommandé
- The AFS750-30-12-70 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The AFS750-30-12-68 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The AFS750-30-12-69 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.