MPN
1SFL577081R6812
Weight
10.6 kg
The AFS400-30-12-68 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 200 kW / 400 V AC (AC-3) or 350 hp / 480 V UL and switching power circuits up to 600 A (AC-1) or 550 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

AFS contactors for safety applications

AFS contactors are specifically designed to enhance safety in machine applications. Featuring factory-mounted contact blocks with mechanically linked and mirror contacts, these contactors ensure reliable monitoring and control of circuits. With ABB’s comprehensive safety component range, building protection systems becomes more straightforward and efficient.

Main Benefits:

  • Safety Compliance: Meets major safety standards (EN ISO 13849 and EN 62061) for secure machinery and equipment use.

  • Guaranteed Status: Factory-mounted auxiliary contact blocks ensure accurate contactor status monitoring.

  • Easy Identification: Distinct yellow housing simplifies safety chain recognition.

  • Streamlined Safety Calculations: Safety values available in FSDT and Sistema tools for easier safety level assessments.

Main Features:

  • High Power Handling:

    • Up to 400 kW at 400 V AC-3

    • Up to 600 hp at 480 V

    • Up to 1050 A at 690 V AC-1

    • Up to 900 A for general use

  • Certified Safety Contacts: Mirror and mechanically linked contacts with third-party certification.

  • Fast Response: Opening times as low as 20 ms in certain models with PLC interfaces.

  • Precision Switching: Low-energy auxiliary contacts with a minimum switching capacity of 12 V, 3 mA (10⁻⁷).

  • Built-in Protection: Integrated surge suppression for enhanced safety.

Spécifications techniques

Dimensions

Produit Largeur Net186 mm
Produit Longueur Net216 mm
Produit Hauteur Net278 mm
Poids net10,6 kg

Technique

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC2
TensionCircuit principal 1000 V
Fréquence assignée (f)Circuit principal 50 / 60 Hz
Courant thermique conventionnel à l’air libre (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 600 A
Courant assignée d’emploi AC-1 (Ie)(1000 V) 40 °C 600 A, (1000 V) 55 °C 500 A, (1000 V) 70 °C 400 A, (690 V) 40 °C 600 A, (690 V) 55 °C 500 A, (690 V) 70 °C 400 A
Courant assignée d’emploi AC-3 (Ie)(415 V) 55 °C 400 A, (440 V) 55 °C 400 A, (500 V) 55 °C 400 A, (690 V) 55 °C 350 A, (1000 V) 55 °C 155 A, (380 / 400 V) 55 °C 400 A, (220 / 230 / 240 V) 55 °C 400
Puissance assignée d’emploi AC-3 (Pe)(415 V) 220 kW, (440 V) 220 kW, (500 V) 250 kW, (690 V) 315 kW, (1000 V) 220 kW, (380 / 400 V) 200 kW, (220 / 230 / 240 V) 110 kW
Pouvoir assigné de coupure AC-38 x Ie AC-3
Pouvoir assigné de fermeture AC-310 x Ie AC-3
Dispositif de protection contre les courts-circuitsgG Type Fuses 630 A
Courant assigné de courte durée admissible (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4000 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3500 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour, (AC-2 / AC-4) 60 cycles per hour, (AC-3) 300 cycles per hour
Courant assignée d’emploi DC-1 (Ie)(110 V) 1-Pole, 40 °C 600 A, (110 V) 2 Poles in Series, 40 °C 600 A, (220 V) 3 Poles in Series, 40 °C 600 A, (600 V) 3 Poles in Series, 40 °C 600 A
Courant assignée d’emploi DC-3 (Ie)(110 V) 1-Pole, 40 °C 600 A, (110 V) 2 Poles in Series, 40 °C 600 A, (220 V) 3 Poles in Series, 40 °C 600 A, (600 V) 3 Poles in Series, 40 °C 600 A
Courant assignée d’emploi DC-5 (Ie)(110 V) 1-Pole, 40 °C 600 A, (110 V) 2 Poles in Series, 40 °C 600 A, (220 V) 3 Poles in Series, 40 °C 600 A, (600 V) 3 Poles in Series, 40 °C 600 A
Tension assignée d’isolement (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V
Tension assignée de tenue aux chocs (Uimp)Circuit principal 8 kV
Durabilite mecanique5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Plage d'utilisation de la bobine selon(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)DC Operation 24 ... 60 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A, Holding at Max. Rated Control Circuit Voltage DC 7.5 V·A, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 900 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 900 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 900 V·A
Durée de fonctionnement nominaleEntre la mise hors tension de la bobine et la fermeture du contact NC (normally closed) 45 ... 55 ms, Entre la mise hors tension de la bobine et l'ouverture du contact NO (normally open) 48 ... 58 ms, Entre la mise sous tension de la bobine et l'ouverture du contact NC 45 ... 115 ms, Entre la mise sous tension de la bobine et la fermeture du contact NO 50 ... 120 ms
Connecting Capacity Main CircuitBar 47 mm², Rigid Al-Cable 240 mm², Rigid Cu-Cable 240 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Flexible 1x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm²
Indice de protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Type de borneMain Circuit: Bars

Technique UL/CSA

Maximum Operating Voltage UL/CSACircuit principal 600 V
General Use Rating UL/CSA(600 V AC) 550 A
Puissance nominale UL/CSA(200 ... 208 V AC) Three Phase 125 hp, (220 ... 240 V AC) Three Phase 150 hp, (440 ... 480 V AC) Three Phase 350 hp, (550 ... 600 V AC) Three Phase 400 hp

Environnement

Température de l’air ambiantClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C, Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C, Close to Contactor for Storage -40 ... +70 °C
Altitude de fonctionnement maximale autoriséeWithout Derating 3000 m
Statut RoHSFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Pourquoi Proax pour ABB AFS400-30-12-68?

Proax est un distributeur autorisé de ABB AFS400-30-12-68 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!

Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!

Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
Autres nomsAFS400301268
Taille de l'emballage1
Recommandé

Pas en stock

Demandez un délai de livraison ou commandez - nous assurerons une livraison rapide

ABB Disponibilité