By ABB
AFS contactors for safety applications
AFS contactors are specifically designed to enhance safety in machine applications. Featuring factory-mounted contact blocks with mechanically linked and mirror contacts, these contactors ensure reliable monitoring and control of circuits. With ABB’s comprehensive safety component range, building protection systems becomes more straightforward and efficient.
Main Benefits:
Safety Compliance: Meets major safety standards (EN ISO 13849 and EN 62061) for secure machinery and equipment use.
Guaranteed Status: Factory-mounted auxiliary contact blocks ensure accurate contactor status monitoring.
Easy Identification: Distinct yellow housing simplifies safety chain recognition.
Streamlined Safety Calculations: Safety values available in FSDT and Sistema tools for easier safety level assessments.
Main Features:
High Power Handling:
Up to 400 kW at 400 V AC-3
Up to 600 hp at 480 V
Up to 1050 A at 690 V AC-1
Up to 900 A for general use
Certified Safety Contacts: Mirror and mechanically linked contacts with third-party certification.
Fast Response: Opening times as low as 20 ms in certain models with PLC interfaces.
Precision Switching: Low-energy auxiliary contacts with a minimum switching capacity of 12 V, 3 mA (10⁻⁷).
Built-in Protection: Integrated surge suppression for enhanced safety.
Dimensions
Produit Largeur Net | 70 mm |
Produit Longueur Net | 149 mm |
Produit Hauteur Net | 125,5 mm |
Poids net | 1,22 kg |
Technique
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 2 |
Number of Auxiliary Contacts NC | 2 |
Tension | Circuit auxiliaire 690 V, Circuit principal 1000 V |
Fréquence assignée (f) | Circuit auxiliaire 50 / 60 Hz, Circuit principal 50 / 60 Hz |
Courant thermique conventionnel à l’air libre (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 130 A, acc. to IEC 60947-5-1, q = 40 °C 16 A |
Courant assignée d’emploi AC-1 (Ie) | (690 V) 40 °C 130 A, (690 V) 60 °C 105 A, (690 V) 70 °C 90 A |
Courant assignée d’emploi AC-3 (Ie) | (415 V) 60 °C 96 A, (440 V) 60 °C 96 A, (500 V) 60 °C 80 A, (690 V) 60 °C 57 A, (1000 V) 60 °C 30 A, (380 / 400 V) 60 °C 105 A, (220 / 230 / 240 V) 60 °C 105 A |
Courant assignée d’emploi AC-3e (Ie) | (415 V) 60 °C 96 A, (440 V) 60 °C 96 A, (500 V) 60 °C 80 A, (690 V) 60 °C 57 A, (380 / 400 V) 60 °C 105 A, (220 / 230 / 240 V) 60 °C 105 A |
Puissance assignée d’emploi AC-3 (Pe) | (415 V) 55 kW, (440 V) 55 kW, (500 V) 55 kW, (690 V) 55 kW, (1000 V) 40 kW, (380 / 400 V) 45 kW, (380 / 400 V) 55 kW, (220 / 230 / 240 V) 25 kW, (220 / 230 / 240 V) 30 kW |
Puissance assignée d’emploi AC-3e (Pe) | (415 V) 55 kW, (440 V) 55 kW, (500 V) 55 kW, (690 V) 55 kW, (380 / 400 V) 45 kW, (380 / 400 V) 55 kW, (220 / 230 / 240 V) 25 kW, (220 / 230 / 240 V) 30 kW |
Courant assignée d’emploi AC-15 (Ie) | (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A |
Courant assigné de courte durée admissible (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A, for 0.1 s 140 A, for 1 s 100 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour, (AC-15) 1200 cycles per hour, (AC-2 / AC-4) 150 cycles per hour, (AC-3) 1200 cycles per hour, (DC-13) 900 cycles per hour |
Courant assignée d’emploi DC-13 (Ie) | (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W |
Tension assignée d’isolement (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
Tension assignée de tenue aux chocs (Uimp) | 8 kV |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V, 60 Hz 100 ... 250 V, DC Operation 100 ... 250 V |
Durée de fonctionnement nominale | Entre la mise hors tension de la bobine et la fermeture du contact NC (normally closed) 19 ... 105 ms, Entre la mise hors tension de la bobine et l'ouverture du contact NO (normally open) 17 ... 100 ms, Entre la mise sous tension de la bobine et l'ouverture du contact NC 38 ... 95 ms, Entre la mise sous tension de la bobine et la fermeture du contact NO 42 ... 100 ms |
Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 screws placed diagonally |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 6 ... 50 mm², Flexible with Insulated Ferrule 1/2x 6 ... 50 mm², Rigid 1x 6 ... 70 mm², Rigid 2x 6 ... 50 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid 1/2x 1 ... 2.5 mm² |
Wire Stripping Length | Auxiliary Circuit 10 mm, Control Circuit 10 mm, Main Circuit 17 mm |
Indice de protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Type de borne | Bornes à vis |
Technique UL/CSA
General Use Rating UL/CSA | (600 V AC) 115 A |
Puissance nominale UL/CSA | (120 V AC) Single Phase 7-1/2 hp, (200 ... 208 V AC) Three Phase 30 hp, (220 ... 240 V AC) Three Phase 40 hp, (240 V AC) Single Phase 20 hp, (440 ... 480 V AC) Three Phase 75 hp, (550 ... 600 V AC) Three Phase 75 hp |
Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb, Control Circuit 11 in·lb, Main Circuit 53 in·lb |
Environnement
Température de l’air ambiant | Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C |
Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Altitude de fonctionnement maximale autorisée | Without Derating 3000 m |
Resistance to Vibrations acc. to IEC 60068-2-6 | 5 ... 300 Hz 3 g closed position / 3 g open position |
Résistance aux chocs selon CEI 60068-2-27 | Closed, Shock Direction: A 25 g, Closed, Shock Direction: B1 25 g, Closed, Shock Direction: B2 15 g, Closed, Shock Direction: C1 25 g, Closed, Shock Direction: C2 25 g |
Statut RoHS | Following EU Directive 2011/65/EU |
Pourquoi Proax pour ABB AFS96-30-22-13?
Proax est un distributeur autorisé de ABB AFS96-30-22-13 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Autres noms | AFS96302213 |
Taille de l'emballage | 1 |
- The AF26-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 11 kW / 400 V AC (AC-3) or 15 hp / 480 V UL and switching power circuits up to 45 A (AC-1) or 45 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The AF16-30-10-13 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) or 10 hp / 480 V UL and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The AF30-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 15 kW / 400 V AC (AC-3) or 20 hp / 480 V UL and switching power circuits up to 50 A (AC-1) or 50 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
- The AF09-30-01-13 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
- The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
- Connecting links with manual motor startersThe BEA insulated 3-pole connecting links are used to connect AF09 ... AF65 contactors with the MS116 or MS132 or MS165 manual motor starters. The BEA insulated 3-pole connecting links ensure the electrical and mechanical connection between the contactor and the associated manual motor starter. BPR65-4 35 mm rail hooks used with BEA65-4 connecting link, allow direct mounting on 2 rails 35 mm of MS165 manual motor starters with AF40 ... AF65 contactors.
- The VEM4 is a mechanical and electrical interlock set for the interlocking of two AF(C) contactors.VEM4 set includes a mechanical interlock unit VM4 with 2 fixing clips (BB4) and a VE4 electrical interlock block with A2-A2 connection.Fixing the electrical interlock block to the contactor front face connects the 2 built-in N.C. interlocking contacts with the two coils. VE4 block must be used with A2-A2 connection to respect the electrical connection diagram.
- The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
- The AF65-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 30 kW / 400 V AC (AC-3) or 50 hp / 480 V UL and switching power circuits up to 105 A (AC-1) or 90 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.