The CM-MPN.72P is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 530-820 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay monitors all phase parameters such as over/undervoltage, phase unbalance and phase failure. The corresponding threshold values are adjustable. The CM-MPN.72P also offers selection of phase sequence monitoring, automatic phase sequence correction as well as an ON or OFF tripping delay. The output contacts can be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signal for over- and undervoltage thresholds) operation. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers maintenance free Easy Connect Technology with push-in terminals.
Spécifications techniques

Dimensions

Produit Largeur Net45 mm
Produit Longueur Net104,8 mm
Produit Hauteur Net85,6 mm
Poids net0,22 kg

Technique

FonctionAutomatic phase sequence correction, Over- and undervoltage monitoring, Phase failure detection, Phase unbalance detection, Phase sequence monitoring
Normes et standardsIEC/EN 63000, IEC/EN 60255-27, IEC/EN 61000-6-2, IEC/EN 61000-6-3
Plage de mesure(L-L) 530 ... 820 V AC
Rated Control Supply Voltage (Us)(L-L) 530 ... 820 V AC
Fréquence assignée (f)Supply Circuit 50/60 Hz
Sortie2 x 1 c/o or 1 x 2 c/o contacts, configurable
Time Range0 s or 0.1 ... 30 s tripping delay (ON or OFF), 200 ms start-up delay
Type de borneBornes sans vis
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Courant assignée d’emploi AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Courant assignée d’emploi DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V, 10 mA
Tension assignée d’isolement (Ui)Input Circuit / Output Circuit 1000 V, Output Circuit 1 / Output Circuit 2 300 V
Tension assignée de tenue aux chocs (Uimp)Input Circuit 8 kV, Output Circuit 4 kV
Indice de protectionHousing IP50, Terminals IP20
Catégorie de surtensionIII
Degré de pollution3
Dispositif de protection contre les courts-circuitsOutput Circuit NC - F Type Fuses 6 A, Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Durabilite mecanique30000000 cycle
Connecting CapacityFlexible with Ferrule 2x 0.5 ... 1.5 mm², Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm², Flexible 2x 0.5 ... 1.5 mm², Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length8 mm
Type d'encastrement1 ... 6
Montage sur rail DINTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715, TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715

Environnement

Température de l’air ambiantOperation -25 ... +60 °C, Storage -40 ... +85 °C
Altitude de fonctionnement maximale autoriséeWithout Derating 2000 m
Statut RoHSFollowing EU Directive 2011/65/EU

Technique UL/CSA

Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 2x 18-16 AWG, Rigid 2x 20-16 AWG

Pourquoi Proax pour ABB CM-MPN.72P?

Proax est un distributeur autorisé de ABB CM-MPN.72P et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!

Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!

Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires

Autres nomsCMMPN72P
Taille de l'emballage1
Recommandé

Pas en stock

Demandez un délai de livraison ou commandez - nous assurerons une livraison rapide

ABB Disponibilité