CM-ESS.2S
By ABB
SKU
ABB1SVR730831R0400
MPN
1SVR730831R0400
Weight
0.204 kg
The CM-ESS.2S is a single-functional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V AC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V and works according to the open-circuit principle. The CM-ESS.2S is configurable for over- or undervoltage monitoring. The hysteresis is adjustable within a range of 3 to 30 % of the threshold value and the tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
Documents
Spécifications techniques
Dimensions
| Produit Largeur Net | 22,5 mm |
| Produit Longueur Net | 103,7 mm |
| Produit Hauteur Net | 85,6 mm |
| Poids net | 0,181 kg |
Technique
| Fonction | Over- or undervoltage monitoring |
| Plage de mesure | 3 ... 30 V, 6 ... 60 V, 30 ... 300 V, 60 ... 600 V |
| Rated Control Supply Voltage (Us) | 110 ... 130 V AC |
| Sortie | 2 contacts c/o (SPDT) |
| Time Range | 0 s or 0.1 ... 30 s tripping delay (ON) |
| Type de borne | Bornes à vis |
| Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
| Courant assignée d’emploi AC-15 (Ie) | (230 V) 3 A |
| Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
| Courant assignée d’emploi DC-13 (Ie) | (24 V) 2 A |
| Minimum Switching Capacity | 24 V, 10 mA |
| Tension assignée d’isolement (Ui) | Measuring Circuit / Output Circuit 600 V, Output Circuit 1 / Output Circuit 2 250 V, Supply Circuit / Measuring Circuit 600 V, Supply Circuit / Output Circuit 250 V |
| Tension assignée de tenue aux chocs (Uimp) | Measuring Circuit / Output Circuit 6 kV, Output Circuit 1 / Output Circuit 2 4 kV, Supply Circuit / Measuring Circuit 6 kV, Supply Circuit / Output Circuit 4 kV |
| Indice de protection | Housing IP50, Terminals IP20 |
| Catégorie de surtension | III |
| Degré de pollution | 3 |
| Dispositif de protection contre les courts-circuits | Output Circuit NC - F Type Fuses 10 A, Output Circuit NO - F Type Fuses 10 A |
| Electrical Durability | AC-12 100000 cycle |
| Durabilite mecanique | 30000000 cycle |
| Connecting Capacity | Flexible with Ferrule 1x 0.5 ... 2.5 mm², Flexible with Ferrule 2x 0.5 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm², Flexible 1x 0.5 ... 2.5 mm², Flexible 2x 0.5 ... 1.5 mm², Rigid 1x 0.5 ... 4 mm², Rigid 2x 0.5 ... 2.5 mm² |
| Couple de serrage | 0.6 ... 0.8 N·m |
| Wire Stripping Length | 8 mm |
| Recommended Screw Driver | Pozidriv 1, 4.5, 0.8 x 4 |
| Type d'encastrement | 1 ... 6 |
| Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Normes et standards | CAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 60255-27, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508 |
Technique UL/CSA
| Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
| Contact Rating UL/CSA | B300 |
| Connecting Capacity UL/CSA | Flexible 1x 18-14 AWG, Flexible 2x 18-16 AWG, Rigid 1x 20-12 AWG, Rigid 2x 20-14 AWG |
| Tightening Torque UL/CSA | 7.08 in·lb |
Environnement
| Température de l’air ambiant | Operation -20 ... +60 °C, Storage -40 ... +85 °C |
| Altitude de fonctionnement maximale autorisée | Without Derating 2000 m |
| Statut RoHS | Following EU Directive 2011/65/EU |
Pourquoi Proax pour ABB CM-ESS.2S?
Proax est un distributeur autorisé de ABB CM-ESS.2S et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
| Autres noms | CMESS2S |
| Taille de l'emballage | 1 |
Recommandé
The CM-ESS.1S is a single-functional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V AC and has a 1 c/o (SPDT) output contact rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 3-60 A, 30-300 V and 60-600 V and works according to the open-circuit principle. The CM-ESS.1S is configurable for over- or undervoltage monitoring, the hysteresis is adjustable within a range of 3 to 30 % of the threshold value. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
The CM-ESS.2S is a single-functional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 220 - 240 V AC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V and works according to the open-circuit principle. The CM-ESS.2S is configurable for over- or undervoltage monitoring. The hysteresis is adjustable within a range of 3 to 30 % of the threshold value and the tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.