2CDS271337R0104
SU201M-C10 Miniature Circuit Breaker C-Char., 10kA, 10A, 1P UL489
Spécifications techniques
Technique
Normes et standards | CSA 22.2 No. 5, IEC/EN 60947-2, UL 489 |
Tripping Characteristic | C |
Tension | acc. to IEC 60898-1 277 V, acc. to IEC 60947-2 230 V AC |
Tension assignée d’isolement (Ui) | acc. to IEC/EN 60664-1 440 V |
Tension assignée de tenue aux chocs (Uimp) | 4 kV, at 2000 m 5 kV, at Sea Level 6.2 kV |
Type de tension | AC/DC |
Courant nominal (IN) | 10 A |
Rated Short-Circuit Capacity | (230 V AC) 11.2 kA |
Pouvoir assigné de coupure ultime en court-circuit (Icu) | (230 V AC) 15 kA |
Rated Conditional Short-Circuit Current (Inc) | (230 V) 15 kA |
Pourvoir assigné de coupure de service en court-circuit (Ics) | (230 V AC) 11.2 kA |
Fréquence assignée (f) | 50 / 60 Hz, DC |
Power Loss | 2.1 W, at Rated Operating Conditions per Pole 2.1 W |
Power Supply Connection | Arbitrary |
Contact Position Indication | Red ON / Green OFF |
Classe de limitation d'énergie | 3 |
Mechanical Endurance | 20000 cycle |
Nombre de pôles | 1 |
Number of Protected Poles | 1 |
Catégorie de surtension | III |
Couple de serrage | 2.8 N·m |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
Actuator Marking | I / O |
Actuator Material | Insulation Group II, Black, Sealable |
Qualité du matériau | Insulation Group I, RAL 7035 |
Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Type d'encastrement | tous |
Recommended Screw Driver | Pozidriv 2 |
Accessories Available | Oui |
Connecting Capacity | Busbar 10 / 10 mm², Flexible with Ferrule 0.75 ... 25 mm², Flexible 0.75 ... 25 mm², Rigid 0.75 ... 35 mm², Stranded 0.75 ... 35 mm² |
Installation Size | acc. to DIN 43880 3 |
Type de borne | Double Clamp |
Environnement
Température de l’air ambiant | Operation -25 ... +55 °C, Storage -40 ... +70 °C |
Indice de protection | IP20, Enclosure with Cover IP40 |
Degré de pollution | 3 |
Environmental Conditions | 28 cycles, with 55 °C / 90-96 %, and 25 °C / 95-100 % |
Resistance to Vibrations acc. to IEC 60068-2-6 | 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In |
Résistance aux chocs selon CEI 60068-2-27 | 25g / 2 shocks / 13 ms |
Statut RoHS | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
REACH Declaration | 9AKK107492A1906 |
Technique UL/CSA
Maximum Operating Voltage UL/CSA | 277 V AC, 48 V DC |
Interrupting Rating acc. to UL489 | (240 V AC) 10 kA, (277 V AC) 10 kA, (48 V DC) 10 kA |
Connecting Capacity UL/CSA | Busbar 18-8 AWG, Conductor 18-4 AWG |
Dimensions
Width in Number of Modular Spacings | 1 |
Produit Largeur Net | 17,5 mm |
Produit Hauteur Net | 111 mm |
Produit Longueur Net | 69 mm |
Poids net | 0,125 kg |
Pole Net Weight | 0,125 kg |
Profondeur d'encastrement (t2) | 69 mm |
Pourquoi Proax pour ABB SU201M-C10?
Proax est un distributeur autorisé de ABB SU201M-C10 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
Autres noms | SU201MC10 |
Taille de l'emballage | 1 |
Recommandé