AF09B-22-00-14
By ABB
Documents
AF 4-pole Contactors
Secure uptime and optimize stock management with AF technology, offering superior performance and energy savings (up to 80% reduction). The electronically controlled coil ensures stability against voltage drops and sags, while ABB’s global product range simplifies logistics.
Key Features:
Up to 1000 A, 690 V AC-1 and 540 A, 600 V general use
Wide voltage range: 24 V - 500 V AC / 20 V - 500 V DC
Built-in surge suppression
Snap-to-connect accessories for easy installation
Mirror and mechanically linked contacts for safety
Dimensions
| Produit Largeur Net | 45 mm |
| Produit Longueur Net | 77 mm |
| Produit Hauteur Net | 86 mm |
| Poids net | 0,31 kg |
Technique
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Normes et standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Tension | Circuit principal 690 V |
| Courant thermique conventionnel à l’air libre (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A |
| Courant assignée d’emploi AC-1 (Ie) | (1000 V) 60 °C 25 A, (690 V) 40 °C 25 A, (690 V) 70 °C 22 A |
| Courant assignée d’emploi AC-3 (Ie) | (415 V) 60 °C 9 A, (440 V) 60 °C 9 A, (500 V) 60 °C 9.5 A, (690 V) 60 °C 7 A, (380 / 400 V) 60 °C 9 A, (220 / 230 / 240 V) 60 °C 9 A |
| Puissance assignée d’emploi AC-3 (Pe) | (400 V) 4 kW, (415 V) 4 kW, (440 V) 4 kW, (500 V) 5.5 kW, (690 V) 5.5 kW, (380 / 400 V) 4 kW, (220 / 230 / 240 V) 2.2 kW |
| Courant assigné de courte durée admissible (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A |
| Tension assignée d’isolement (Ui) | acc. to UL/CSA 600 V |
| Tension assignée de tenue aux chocs (Uimp) | 6 kV |
| Rated Control Circuit Voltage (Uc) | 50 Hz 250 ... 500 V, 60 Hz 250 ... 500 V, DC Operation 250 ... 500 V |
| Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm², Flexible with Insulated Ferrule 1x 0.75 ... 4 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 6 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid 1/2x 1 ... 2.5 mm² |
| Indice de protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
| Type de borne | Bornes à vis |
Technique UL/CSA
| General Use Rating UL/CSA | (600 V AC) 25 A |
Environnement
| Température de l’air ambiant | Close to Contactor for Storage -60 ... +80 °C, Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Altitude de fonctionnement maximale autorisée | Without Derating 3000 m |
| Statut RoHS | Following EU Directive 2011/65/EU |
Pourquoi Proax pour ABB AF09B-22-00-14?
Proax est un distributeur autorisé de ABB AF09B-22-00-14 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
| Autres noms | AF09B220014 |
| Taille de l'emballage | 1 |
The AF09B-22-00RT-14 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-30-01-14 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-30-10-14 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-30-01RT-14 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-30-10RT-14 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-40-00-14 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF09B-40-00RT-14 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.