TTC-6P-2X1-F-M-24DC-UT-I - Surge protection device
Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., Digital IN/OUT. Indirect grounding via gas-filled surge arrester.
- Space-saving and cost-saving with a narrow overall width of just 6 mm
- Continuous monitoring of protective devices, plus mechanical status indicator with optional remote signaling
- Finding the right product for all possible requirements in MCR applications is easy, thanks to the complete range of products with customized features
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Spécifications techniques
Hauteur | 105.8 |
Largeur | 6,2 +0,1 mm |
Profondeur | 100 (rail DIN 7,5 mm inclus) |
Température ambiante (fonctionnement) | -40 °C ... 85 °C |
Température ambiante (stockage/transport) | -40 °C ... 85 °C |
Humidité admissible (fonctionnement) | 5 % ... 95 % |
Altitude | ≤ 4000 m (au-dessus du niveau moyen de la mer) |
Degré de protection | IP20 |
Matériau du boîtier | PBT |
Indice d'inflammabilité selon UL 94 | V-0 |
Couleur | gris trafic A RAL 7042 |
Couleur | gris clair RAL 7035 |
Type de montage | Rail DIN : TH 35 - 7,5 mm |
Type | Module de rail DIN, à deux sections, divisible |
Direction de l'action | Ligne-ligne et ligne-terre de signal/bouclier et terre de signal optionnelle/bouclier-terre |
Classification d'essai CEI | C1 |
Classification d'essai CEI | C2 |
Classification d'essai CEI | C3 |
Classification d'essai CEI | D1 |
Tension nominale UN | 24 V DC |
Tension continue maximale UC | 30 V DC |
Tension continue maximale UC | 21 |
Courant nominal | 600 mA (56 °C) |
Courant effectif de fonctionnement IC à UC | ≤ 5 µA |
Courant résiduel IPE | ≤ 1 µA |
Courant de décharge nominal In (8/20) µs (ligne-terre) | 5 kA |
Courant de décharge nominal In (8/20) µs (ligne-signal à la terre) | 5 kA |
Courant de décharge de l'impulsion Iimp (10/350) µs (ligne-terre) | 0,5 kA |
Courant de décharge de l'impulsion Iimp (10/350) µs (ligne-masse du signal) | 0,5 kA |
Courant de décharge total Itotal (8/20) µs | 10 kA |
Niveau de protection de la tension Up (ligne-terre) | ≤ 750 V (C1 - 1 kV / 500 A) |
Niveau de protection de la tension Up (ligne-terre) | ≤ 800 V (C2 - 10 kV / 5 kA) |
Niveau de protection de la tension Up (ligne-terre) | ≤ 1,1 kV (C3 - 25 A) |
Niveau de protection de la tension Up (ligne-terre) | ≤ 1,15 kV (C3 - 100 A) |
Niveau de protection de la tension Up (ligne-terre de signal) | ≤ 140 V (C1 - 1 kV / 500 A) |
Niveau de protection de la tension Up (ligne-terre de signal) | ≤ 190 V (C2 - 10 kV / 5 kA) |
Niveau de protection de la tension Up (ligne-terre de signal) | ≤ 45 V (C3 - 25 A) |
Niveau de protection de la tension Up (ligne-terre de signal) | ≤ 50 V (C3 - 100 A) |
Niveau de protection de la tension Up statique (ligne-terre) | ≤ 750 V (C1 - 1 kV / 500 A) |
Niveau de protection de la tension Up statique (ligne-terre) | ≤ 800 V (C2 - 10 kV / 5 kA) |
Niveau de protection de la tension Up statique (ligne-plan de signal) | ≤ 55 V (C1 - 1 kV / 500 A) |
Niveau de protection de la tension Up statique (ligne-plan de signal) | ≤ 120 V (C2 - 10 kV / 5 kA) |
Temps de réponse tA (ligne-signal de fond) | ≤ 1 ns |
Temps de réponse tA (ligne-terre) | ≤ 100 ns |
Atténuation d'entrée aE, asym. | typ. 0,3 dB (≤ 270 kHz/150 Ω) |
Fréquence de coupure fg (3 dB), asymétrique (masse du signal) dans un système de 150 Ω | typ. 960 kHz |
Capacité (ligne-signal-plan) | typ. 2,2 nF |
Résistance par chemin | 1.65 Ω ±20 % |
Message de défaut de la protection contre les surtensions | optique |
Fusible de secours max. requis | 630 mA (FF) |
Durabilité de l'impulsion (ligne-terre) | C1 - 1 kV / 500 A |
Durabilité de l'impulsion (ligne-terre) | C2 - 10 kV / 5 kA |
Durabilité de l'impulsion (ligne-terre) | C3 - 100 A |
Durabilité de l'impulsion (ligne-terre) | D1 - 500 A |
Durabilité de l'impulsion (ligne-signal de fond) | C1 - 1 kV / 500 A |
Durabilité de l'impulsion (ligne-signal de fond) | C2 - 10 kV / 5 kA |
Durabilité de l'impulsion (ligne-signal de fond) | C3 - 100 A |
Durabilité de l'impulsion (ligne-signal de fond) | D1 - 500 A |
Temps de réinitialisation de l'impulsion (ligne-terre) | ≤ 30 ms |
Temps de réinitialisation de l'impulsion (ligne-signal de fond) | ≤ 300 ms |
Courant de décharge total maximal I total max (8/20) µs | 20 kA (1x) |
Méthode de connexion | Raccordement à vis |
Filet de vis | M3 |
Couple de serrage | 0,5 Nm ... 0,6 Nm |
Longueur de dénudage | 8 |
Section transversale du conducteur flexible | 0.2 ... 2.5 |
Section transversale du conducteur solide | 0.2 ... 4 |
Section du conducteur AWG | 24 ... 12 |
Normes/spécifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modifiée + A2:2012 |
Normes/spécifications | EN 61643-21 2001 + A1:2009 + A2:2013 |
REACh SVHC | Plomb 7439-92-1 |
Chine RoHS | Respectueux de l'environnement Durée d'utilisation = 50 ans |
Chine RoHS | Pour plus d'informations sur les substances dangereuses, voir l'onglet "Téléchargements", catégorie "Déclaration du fabricant". |
Accessories
Pourquoi Proax pour Phoenix Contact 2906784?
Proax est le distributeur autorisé de Phoenix Contact 2906784. Chez Proax, nous sommes l'un des plus grands distributeurs de Phoenix Contact en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
Taille de l'emballage | 1 |
Recommandé