The VBC6A-30-10-P mini reversing contactor is a compact 3 pole contactor with 1 auxiliary contact, soldering pins and mechanical interlock and safety blocking. They are ideally suited for applications where reliability is a must and space is at a premium. Mini reversing contactors are used in residential buldings, commercial buildings and industrial applications for the control of three-phase motor loads up to 4 kW (AC-3). Further features are the noiseless and hum-free coil, a switch position indication and the integrated possibility for rail mounting.
Spécifications techniques
Dimensions
| Produit Largeur Net | 96,2 mm |
| Produit Hauteur Net | 57,5 mm |
| Produit Longueur Net | 47,7 mm |
| Poids net | 0,345 kg |
Technique
| Nombre de pôles | 3 |
| Tension | Circuit auxiliaire 690 V AC, Circuit auxiliaire 250 V DC, Circuit principal 690 V AC, Circuit principal 220 V DC |
| Fréquence assignée (f) | Circuit de commande DC, Circuit principal 60 Hz, Circuit principal 50 Hz, Circuit principal DC |
| Tension assignée de tenue aux chocs (Uimp) | Circuit principal 6 kV |
| Tension assignée d’isolement (Ui) | 690 V, acc. to UL/CSA 600 V |
| Number of Main Contacts NC | 0 |
| Number of Main Contacts NO | 3 |
| Courant assignée d’emploi AC-1 (Ie) | (220 / 240 V) 40 °C 12 A, (220 / 240 V) 55 °C 12 A, (380 / 440 V) 40 °C 12 A, (380 / 440 V) 55 °C 12 A, (690 V) 40 °C 6 A, (690 V) 55 °C 6 A |
| Puissance assignée d’emploi AC-3 (Pe) | (230 V) Three Phase 2.2 kW, (400 V) Three Phase 4 kW, (500 V) Three Phase 4 kW, (690 V) Three Phase, NO 3 kW |
| Courant assigné de courte durée admissible (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A |
| Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Courant assignée d’emploi AC-15 (Ie) | (440 V AC) 3 A, (24 V) 4 A, (120 V) 4 A, (240 V) 4 A, (500 V) 2 A, (380 / 400 V) 3 A |
| Courant assignée d’emploi DC-13 (Ie) | (24 V) 2.5 A, (110 V) 0.7 A, (220 / 240 V) 0.4 A |
| Courant thermique conventionnel à l’air libre (Ith) | Main Circuit 12 A |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Plage d'utilisation de la bobine selon | (acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Indice de protection | Auxiliary Circuit Terminals IP20, Control Circuit Terminals IP20, Main Circuit Terminals IP20 |
| Degré de pollution | 3 |
| Durabilite mecanique | 10000000 cycle |
| Minimum Switching Capacity | Auxiliary Circuit 17 V, Auxiliary Circuit 5 mA |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-15) 600 cycles per hour, (AC-3) 600 cycles per hour, (DC-1) 600 cycles per hour, (DC-13) 600 cycles per hour, (DC-3) 600 cycles per hour |
| Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Power Loss | at Rated Operating Conditions per Pole 2 W, at Rated Operating Conditions AC-1 per Pole 1 W |
| Normes et standards | IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1 |
Technique UL/CSA
| Maximum Operating Voltage UL/CSA | Circuit principal 600 V AC |
| Full Load Amps Motor Use | (115 V AC) Single Phase 5.8 A, (200 V AC) Three Phase 4.8 A, (220 ... 240 V AC) Three Phase 6.8 A, (230 V AC) Single Phase 4.9 A, (440 ... 480 V AC) Three Phase 4.8 A, (550 ... 600 V AC) Three Phase 1.7 A |
| Puissance nominale UL/CSA | (115 V AC) Single Phase 0.25 Hp, (200 V AC) Three Phase 1 Hp, (220 ... 240 V AC) Three Phase 2 Hp, (230 V AC) Single Phase 0.5 Hp, (440 ... 480 V AC) Three Phase 3 Hp, (550 ... 600 V AC) Three Phase 1 Hp |
| General Use Rating UL/CSA | (300 V AC) 8 A |
| Contact Rating UL/CSA | A600 |
Environnement
| Température de l’air ambiant | Operation -20 ... +55 °C, Storage -40 ... +80 °C |
| Altitude de fonctionnement maximale autorisée | 2000 m |
| Résistance aux chocs selon CEI 60068-2-27 | 11 ms Pulse 15g |
| Resistance to Vibrations acc. to IEC 60068-2-6 | 5g / 5 ... 150 Hz |
| Statut RoHS | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Pourquoi Proax pour ABB VBC6A-30-10-P-01?
Proax est un distributeur autorisé de ABB VBC6A-30-10-P-01 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
| Autres noms | VBC6A3010P01 |
| Taille de l'emballage | 1 |
Meilleurs vendeursdans Contacteurs
The AF26-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 11 kW / 400 V AC (AC-3) or 15 hp / 480 V UL and switching power circuits up to 45 A (AC-1) or 45 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF16-30-10-13 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) or 10 hp / 480 V UL and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF30-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 15 kW / 400 V AC (AC-3) or 20 hp / 480 V UL and switching power circuits up to 50 A (AC-1) or 50 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
The AF09-30-01-13 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
Connecting links with manual motor startersThe BEA insulated 3-pole connecting links are used to connect AF09 ... AF65 contactors with the MS116 or MS132 or MS165 manual motor starters. The BEA insulated 3-pole connecting links ensure the electrical and mechanical connection between the contactor and the associated manual motor starter. BPR65-4 35 mm rail hooks used with BEA65-4 connecting link, allow direct mounting on 2 rails 35 mm of MS165 manual motor starters with AF40 ... AF65 contactors.
The VEM4 is a mechanical and electrical interlock set for the interlocking of two AF(C) contactors.VEM4 set includes a mechanical interlock unit VM4 with 2 fixing clips (BB4) and a VE4 electrical interlock block with A2-A2 connection.Fixing the electrical interlock block to the contactor front face connects the 2 built-in N.C. interlocking contacts with the two coils. VE4 block must be used with A2-A2 connection to respect the electrical connection diagram.
The auxiliary contact blocks are used for the operation of auxiliary circuits and control circuits for standard industrial environments.Types of auxiliary contact blocks for front mounting:• CA4 1 or 4-pole block, with instantaneous N.O., N.C. contacts• CC4 1-pole block, with N.O. leading contact or N.C. lagging contact• CAT4 2-pole block, with instantaneous N.O. + N.C. contacts and A1 / A2 coil terminal connection on front face.Select the 4-pole auxiliary contact blocks CA4-..E, CA4-..M, CA4-..U or CA4-..N type, according to the contactor or contactor relay type for compliance with the standard requirements (see "Terminal marking and positioning").Types of auxiliary contact blocks for side mounting:• CAL4 2-pole block, with instantaneous N.O. + N.C. contacts.For clipping onto the right- and/or left-hand side of the contactors. The auxiliary contact blocks are equipped with screw type connecting terminals delivered open, protected against accidental direct contact and bear the corresponding function marking.
The AF65-30-00-13 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 30 kW / 400 V AC (AC-3) or 50 hp / 480 V UL and switching power circuits up to 105 A (AC-1) or 90 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.