OTR36T3B
By ABB
SKU
ABBOTR36T3B
MPN
1SCA022572R0320
Weight
1.9 kg
Safety switch, 3-p. 415V AC23 45A, 22kW. Mounted auxiliary contact: 1NO0NC. Stainless steel enclosure. IP65. Black Selector handle. Interlocked cover. Defeatable interlocking. The enclosure of the OTR series is made of rigid stainless steel, class AISI304. The enclosure has a hinged door, with door lock. The cover is interlocked, and can not be opened when switch is on. The interlock function can be defeated for thermographing. Suitable for outdoor and indoor use. The cable entries are of knock out types. PE terminal and auxiliary contact included. Can be used in EMC application, if EMC cable glands are used.
Spécifications techniques
Circular Value
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC340076D0201 |
| Informations RoHS | 1SCC340075D0201 |
Dimensions
| Produit Largeur Net | 150 mm |
| Produit Hauteur Net | 200 mm |
| Produit Longueur Net | 100 mm |
| Poids net | 1,9 kg |
Technique
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 63 A, (500 V) 63 A, (690 V) 63 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 45 A, (500 V) 45 A, (690 V) 20 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 22 kW, (500 V) 22 kW, (690 V) 15 kW |
| Conventional Thermal Current (Ithe) | Fully Enclosed 63 A |
| Tension assignée d’isolement (Ui) | acc. to IEC/EN 60664-1 750 V |
| Tension | Circuit principal 750 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 2.1 kA |
| Courant assigné de courte durée admissible (Icw) | for 1 s 1.5 kA |
| Power Loss | at Rated Operating Conditions per Pole 4.5 W |
| Degré de pollution | 3 |
| Handle Color | Noir |
| Handle Type | Selector handle |
| Position of Line Terminals | Top In - Bottom Out |
| Normes et standards | IEC 60947-1, -3 |
| Fonctions spéciales | EMC |
| Nombre de pôles | 3 |
| Neutral Type | No neutral terminal |
| Connecting Capacity Main Circuit | Screw Clamp 1.5 ... 35 mm², Screw Clamp / PE Terminal 2pc,1.5 ... 25 mm² |
| Section de câble | 1.5 ... 35 mm² |
| Cable Entry Position | Down/Down |
| Cable Outlets Per Side | Blank / B-flange |
| Indice de protection | acc. to IEC 60529 IP65 |
| Résistance aux chocs | Housing IK09 |
| Matériau du boîtier | Acier inoxydable |
| Maximum Mounted Auxiliary Contacts | 2 NO, 1 NC |
| Mounted Auxiliary Contacts | 1 NO, 0 NC |
| Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Position of PE Terminals | Top In - Bottom Out |
| Couple de serrage | Main Circuit 2 N·m |
Technique UL/CSA
| Couple de serrage | Main Circuit 2 N·m |
Environnement
| Statut RoHS | Following EU Directive 2011/65/EU |
Pourquoi Proax pour ABB OTR36T3B?
Proax est un distributeur autorisé de ABB OTR36T3B et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
| Taille de l'emballage | 1 |