CAL4-11K is a 2-pole side mounted auxiliary contact block equipped with Push-In Spring terminals and can be fitted on AF(C)09(Z)(B)...96 contactors and NF(C)(Z)(B) contactor relays. CAL4 auxiliary contact block can be clipped onto the right- and/or left-hand side of the contactors or the contactor relays and bears the corresponding function marking. CAL4-11K is available with 1 N.O. and 1 N.C. instantaneous contacts for standard industrial environments. With the Push-in Spring terminals, one push is all you need for a faster than ever installation, an easier than ever wiring and a reliable as ever connection.
Spécifications techniques

Dimensions

Produit Largeur Net12 mm
Produit Longueur Net60 mm
Produit Hauteur Net72 mm
Poids net0,03 kg

Technique

Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.5 ... 2.5 mm², Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm², Flexible 1/2x 0.5 ... 2.5 mm², Rigid 1/2x 1 ... 2.5 mm²
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour, (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Mounted Auxiliary Contacts1 NO, 1 NC
Type de montageMontage latéral
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Fréquence assignée (f)Circuit auxiliaire 50 / 60 Hz
Tension assignée de tenue aux chocs (Uimp)6 kV
Tension assignée d’isolement (Ui)acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V, acc. to UL/CSA 600 V
Courant assignée d’emploi AC-15 (Ie)(500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A
Courant assignée d’emploi DC-13 (Ie)(24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W
TensionCircuit auxiliaire 690 V
Courant assigné de courte durée admissible (Icw)for 0.1 s 140 A, for 1 s 100 A
Normes et standardsIEC/EN 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1-14
Adapté pourAF09, AF09Z, AF12, AF12Z, AF16, AF16Z, AF26, AF26Z, AF30, AF30Z, AF38, AF38Z, AF40, AF52, AF65, AF80, AF96, AFC09, AFC12, AFC16, AFC26, AFC30, AFC38, AF09B, AF09ZB, AF12B, AF12ZB, AF16B, AF16ZB, AF26B, AF26ZB, AF30B, AF30ZB, AF38B, AF38ZB, NF22E, NFZ22E, NF31E, NFZ31E, NF40E, NFZ40E, NF44E, NFZ44E, NF53E, NFZ53E, NF62E, NFZ62E, NF71E, NFZ71E, NF80E, NFZ80E, NF33/11, NF51/11, NFC22E, NFC31E, NFC40E, NFC44E, NFC53E, NFC62E, NFC71E, NFC80E, NFC33/11, NFC51/11, NFZB22E, NFB22E, NFZB31E, NFB31E, NFZB40E, NFB40E, NFZB44E, NFB44E, NFZB62E, NFB62E, NFZB80E, NFB80E
Type de bornePush-in Spring Terminals
Wire Stripping LengthAuxiliary Circuit 10 mm

Technique UL/CSA

Pilot Duty UL/CSAA600, Q600

Environnement

Courant thermique conventionnel à l’air libre (Ith)acc. to IEC 60947-5-1, q = 40 °C 16 A
Indice de protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Informations RoHS2CMT2021-006277
DEEE B2C / B2BBusiness To Business

Pourquoi Proax pour ABB CAL4-11K?

Proax est un distributeur autorisé de ABB CAL4-11K et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!

Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!

Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires

Autres nomsCAL411K
Taille de l'emballage1
Recommandé

Pas en stock

Demandez un délai de livraison ou commandez - nous assurerons une livraison rapide

ABB Disponibilité