The circuit breaker for transformer protection MS132-0.16T is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 0.16 A. It allows fuse-less protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and a trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, power in-feed blocks and terminal spacers are available as accessory.
Spécifications techniques

Dimensions

Produit Largeur Net45 mm
Produit Hauteur Net90 mm
Produit Longueur Net86.75 mm
Poids net0,215 kg

Technique

Pourvoir assigné de coupure de service en court-circuit (Ics)(230 V AC) 100 kA, (400 V AC) 100 kA
Pouvoir assigné de coupure ultime en court-circuit (Icu)(400 V AC) 100 kA
Courant assigné instantané de réglage de court-circuit (Ii)3.2 A
Setting Range0.10 ... 0.16 A
TensionCircuit principal 690 V AC
Courant nominal de fonctionnement (Ie)0.16 A
Fréquence assignée (f)Circuit principal 50 Hz, Circuit principal 60 Hz
Tension assignée de tenue aux chocs (Uimp)Circuit principal 6 kV
Tension assignée d’isolement (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.5 W
Nombre de pôles3
Courant thermique conventionnel à l’air libre (Ith)Main Circuit 0.16 A
Indice de protectionHousing IP20, Main Circuit Terminals IP10
Degré de pollution3
Electrical Durability50000 cycle
Durabilite mecanique100000 cycle
Type de borneBornes à vis
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm², Flexible 1/2x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 4 mm²
Couple de serrageMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Recommended Screw DriverPozidriv 2, M3.5
Type d'encastrement1 ... 6
Montage sur rail DINTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm, Other Device Same Type, Horizontal 9 mm, Other Device Same Type, Vertical 150 mm
Actuator TypePOIGNÉE ROTATIVE
Contact Position IndicationON / OFF / TRIP
Normes et standardsIEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1

Technique UL/CSA

Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA, Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSACircuit principal 600 V AC
Full Load Amps Motor Use(120 V AC) Single Phase 0.16 A, (220 ... 240 V AC) Single Phase 0.16 A
Locked Rotor Amps(120 V AC) Single Phase 0.96 A, (220 ... 240 V AC) Single Phase 0.96 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-12 AWG, Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSAMain Circuit 10 ... 12 in·lb

Environnement

Température de l’air ambiantAround the Enclosure 0 ... +40 °C, Operation -25 ... +70 °C, Operation Compensated -25 ... +60 °C, Storage -50 ... +80 °C
Ambient Air Temperature CompensationOui
Altitude de fonctionnement maximale autorisée2000 m
Résistance aux chocs selon CEI 60068-2-2711 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-65g / 3 ... 150 Hz
Statut RoHSFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Pourquoi Proax pour ABB MS132-0.16T?

Proax est un distributeur autorisé de ABB MS132-0.16T et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!

Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!

Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires

Autres nomsMS132016T
Taille de l'emballage1
Recommandé

Pas en stock

Demandez un délai de livraison ou commandez - nous assurerons une livraison rapide

ABB Disponibilité