AF12N0-30-01-12
By ABB
SKU
ABBAF12N0300112
MPN
1SBL157001N1201
Weight
0.27 kg
The AF12N0-30-01-12 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Spécifications techniques
Dimensions
| Produit Largeur Net | 45 mm |
| Produit Longueur Net | 77 mm |
| Produit Hauteur Net | 86 mm |
| Poids net | 0,27 kg |
Technique
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm², Flexible with Insulated Ferrule 1x 0.75 ... 4 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Rigid 1/2x 1 ... 6 mm² |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour, (AC-15) 1200 cycles per hour, (AC-2 / AC-4) 300 cycles per hour, (AC-3) 1200 cycles per hour, (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Minimum Mounting Distance | Other Device Same Type, Horizontal 0 mm, Other Device Same Type, Vertical 0 mm |
| Mounted Auxiliary Contacts | 0 NO, 1 NC |
| Type d'encastrement | Max. N.C. built-in and add-on N.C. auxiliary contacts: see accessory fitting details for a 3-pole contactor AF09 ... AF38 |
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Montage sur rail DIN | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Main Contacts NC | 0 |
| Number of Main Contacts NO | 3 |
| Durée de fonctionnement nominale | Entre la mise hors tension de la bobine et la fermeture du contact NC (normally closed) 13 ... 98 ms, Entre la mise hors tension de la bobine et l'ouverture du contact NO (normally open) 11 ... 95 ms, Entre la mise sous tension de la bobine et l'ouverture du contact NC 38 ... 90 ms, Entre la mise sous tension de la bobine et la fermeture du contact NO 40 ... 95 ms |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1 W, at Rated Operating Conditions AC-3 per Pole 0.2 W |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V, 60 Hz 48 ... 130 V, DC Operation 48 ... 130 V |
| Fréquence assignée (f) | Circuit auxiliaire 50 / 60 Hz, Circuit principal 50 / 60 Hz |
| Tension assignée de tenue aux chocs (Uimp) | 6 kV |
| Tension assignée d’isolement (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V, acc. to UL/CSA 600 V |
| Courant assignée d’emploi AC-1 (Ie) | (690 V) 40 °C 28 A, (690 V) 60 °C 28 A, (690 V) 70 °C 24 A |
| Courant assignée d’emploi AC-15 (Ie) | (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A |
| Courant assignée d’emploi AC-3 (Ie) | (415 V) 60 °C 12 A, (440 V) 60 °C 12 A, (500 V) 60 °C 12.5 A, (690 V) 60 °C 9 A, (380 / 400 V) 60 °C 12 A, (220 / 230 / 240 V) 60 °C 12 A |
| Courant assignée d’emploi AC-3e (Ie) | (415 V) 60 °C 12 A, (440 V) 60 °C 12 A, (500 V) 60 °C 12.5 A, (690 V) 60 °C 9 A, (380 / 400 V) 60 °C 12 A, (220 / 230 / 240 V) 60 °C 12 A |
| Courant assignée d’emploi DC-13 (Ie) | (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W |
| Puissance assignée d’emploi AC-3 (Pe) | (400 V) 5.5 kW, (415 V) 5.5 kW, (440 V) 5.5 kW, (500 V) 7.5 kW, (690 V) 7.5 kW, (380 / 400 V) 5.5 kW, (220 / 230 / 240 V) 3 kW |
| Puissance assignée d’emploi AC-3e (Pe) | (415 V) 5.5 kW, (440 V) 5.5 kW, (500 V) 7.5 kW, (690 V) 7.5 kW, (380 / 400 V) 5.5 kW, (220 / 230 / 240 V) 3 kW |
| Tension | Circuit auxiliaire 690 V, Circuit principal 690 V |
| Courant assigné de courte durée admissible (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A, for 0.1 s 140 A, for 1 s 100 A |
| Normes et standards | IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-16, UL 60947-4-1, CSA C22.2 No. 60947-4-1 |
| Type de borne | Bornes à vis |
| Couple de serrage | Auxiliary Circuit 1.2 N·m, Control Circuit 1.2 N·m, Main Circuit 1.5 N·m |
| Wire Stripping Length | Auxiliary Circuit 10 mm, Control Circuit 10 mm, Main Circuit 10 mm |
Technique UL/CSA
| Continuous Current Rating NEMA | 18 A |
| Full Load Amps Motor Use | (120 V AC) Single Phase 1 A, (200 ... 208 V AC) Three Phase 3 A, (220 ... 240 V AC) Three Phase 3 A, (240 V AC) Single Phase 2 A, (440 ... 480 V AC) Three Phase 7-1/2 A, (550 ... 600 V AC) Three Phase 10 A |
| General Use Rating UL/CSA | (600 V AC) 28 A |
| Horsepower Rating NEMA | (115 V AC) Single Phase 1 Hp, (200 V AC) Three Phase 3 Hp, (230 V AC) Single Phase 2 Hp, (230 V AC) Three Phase 3 Hp, (460 V AC) Three Phase 5 Hp, (575 V AC) Three Phase 5 Hp |
| Puissance nominale UL/CSA | (120 V AC) Single Phase 1 hp, (200 ... 208 V AC) Three Phase 3 hp, (220 ... 240 V AC) Three Phase 3 hp, (240 V AC) Single Phase 2 hp, (440 ... 480 V AC) Three Phase 7-1/2 hp, (550 ... 600 V AC) Three Phase 10 hp |
| NEMA Size | 0 |
| Pilot Duty UL/CSA | A600, Q600 |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb, Control Circuit 11 in·lb, Main Circuit 13 in·lb |
Environnement
| Température de l’air ambiant | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Courant thermique conventionnel à l’air libre (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A, acc. to IEC 60947-5-1, q = 40 °C 16 A |
| Indice de protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
| Altitude de fonctionnement maximale autorisée | Without Derating 3000 m |
| Résistance aux chocs selon CEI 60068-2-27 | Closed, Shock Direction: A 30 g, Closed, Shock Direction: B1 25 g, Closed, Shock Direction: B2 15 g, Closed, Shock Direction: C1 25 g, Closed, Shock Direction: C2 25 g, Open, Shock Direction: A 30 g, Open, Shock Direction: B1 5 g, Open, Shock Direction: B2 15 g, Open, Shock Direction: C1 25 g, Open, Shock Direction: C2 25 g |
| Resistance to Vibrations acc. to IEC 60068-2-6 | 5 ... 300 Hz 4 g closed position / 2 g open position |
| Informations RoHS | 2CMT2021-006277 |
Pourquoi Proax pour ABB AF12N0-30-01-12?
Proax est un distributeur autorisé de ABB AF12N0-30-01-12 et l'un des plus grands distributeurs de ABB en Amérique du Nord. Notre équipe technique interne, qui est hautement qualifiée, est prête à répondre à vos besoins techniques!
Avez-vous une question? pour vous aider à obtenir le bon produit le plus rapidement possible pour votre projet. Nous sommes toujours là pour vous aider!
Délai de livraison court
Personnel qualifié
Chat en direct
Support technique
Inventaire local
60+ ans d'expérience
Informations complémentaires
| Autres noms | AF12N0300112 |
| Taille de l'emballage | 1 |
Recommandé
The AF12N0-30-01-11 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF12N0-30-01-13 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF12N0-30-10-12 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF12N0-30-10-11 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF12N0-30-10-13 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
The AF12N0-30-10-14 is a 3 pole - 600 V UL, NEMA size N0 contactor with 1 built-in auxiliary contact and Screw, switching power circuits up to 28 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.