2938963
SKU
PHX2938963
MPN
QUINT-DIODE/40
Weight
0.683 kg
Series QUINT-DIODE
QUINT-DIODE/40 - Redundancy module
Redundancy module QUINT-DIODE/40
Technical Specifications
DC operation
| Input Voltage | 24 V DC |
| Nominal input voltage range | 24 V DC |
| Input voltage range | 0 V DC ... 30 V DC |
| Input voltage range DC | 0 V DC ... 30 V DC |
| Voltage type of supply voltage | DC |
| Reverse polarity protection | < yes60 V |
| Nominal input current (IN) | 2x 20 A |
| Nominal input current (IN) | 1x 40 A |
| Maximum current Imax | 2x 19 A (6 mm² at 40°C) |
| Maximum current Imax | 1x 39 A (6 mm² at 40°C) |
| Maximum current Imax | 2x 16 A (6 mm² at 60°C) |
| Maximum current Imax | 1x 32 A (6 mm² at 60°C) |
| Maximum current Imax | 2x 27 A (10 mm² at 40°C) |
| Maximum current Imax | 1x 54 A (10 mm² at 40°C) |
| Maximum current Imax | 2x 21 A (10 mm² at 60°C) |
| Maximum current Imax | 1x 43 A (10 mm² at 60°C) |
| Maximum current Imax | 2x 30 A (16 mm² at 40 °C) |
| Maximum current Imax | 1x 60 A (16 mm² at 40 °C) |
| Maximum current Imax | 2x 24 A (16 mm² at 60°C) |
| Maximum current Imax | 1x 48 A (16 mm² at 60°C) |
| Transient surge protection | Transil diode |
| Voltage drop, input/output | 0.5 V |
Output data
| Efficiency | > 97 % |
| Nominal Output Voltage | 24 V DC |
| Nominal output current (IN) | 40 A |
| Power loss nominal load max. | 20 W |
| Connection in series | No |
Input
| Connection Method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Output
| Connection Method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Electrical properties
| Insulation voltage output / PE | 1 kV |
| Insulation voltage input / PE | 1 kV |
| Insulation voltage input, output / housing | 1 kV |
Product properties
| Product family | QUINT DIODE |
| MTBF (IEC 61709, SN 29500) | 28571428 h (40 °C) |
| LED | No |
Insulation characteristics
| Protection class | II (in closed control cabinet) |
| Degree of pollution | 2 |
Dimensions
| Width | 62 mm |
| Height | 84 mm |
| Depth | 102 mm |
| Horizontal pitch | 3.4 Div. |
Installation dimensions
| Installation distance right/left | 5 mm / 5 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | alignable: horizontal 20 mm, vertical 50 mm |
| Mounting Position | horizontal and vertical DIN rail NS 35, EN 60715 |
Material specifications
| Housing Material | Metal |
| Type of housing | AIMg (hood), GD-ZnAICu (cooling unit) |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C derating, -25 ... 60°C) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Standards and Regulations
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standards/specifications | EN 60079-0 |
Approvals
| Shipbuilding approval | DNV GL (EMC A), ABS |
| UL approvals | UL/C-UL listed UL 508 |
| UL approvals | UL/C-UL Recognized UL 60950-1 |
| UL approvals | UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
Conformity/Approvals
| ATEX | II 3G Ex nA IIC T4 Gc |
| ATEX | KEMA 03 ATEX 1197X |
EMC data
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise emission | EN 61000-6-4 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| EMC requirements for noise immunity | EN 61000-6-2 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 55011 |
Why Proax for Phoenix Contact 2938963?
Proax is an authorized distributor of Phoenix Contact 2938963 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
The redundancy set consists of two QUINT-PS/1AC/24DC/10 power supplies combined with the active QUINT-ORING/24DC/2X10/1X20 redundancy module, so as to guarantee maximum availability of your system.Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology, input: 1-phase, output: 24 V DC/10 AActive QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter