2901533
SKU
PHX2901533
MPN
RAD-DAIO6-IFS
Weight
0.201 kg
RAD-DAIO6-IFS - I/O extension module
Radioline - I/O extension module, 2 digital inputs and outputs (0 ... 250 V AC/DC) and 1 analog input (0/4 ... 20 mA) and output (0/4 ... 20 mA, 0 ... 10 V)
- Easy startup via thumbwheel
- Channel-to-channel electrical isolation
- Extended temperature range of -40 °C … +70 °C
- Easy module replacement even during operation (hot swap)
- Digital wide-range inputs/outputs (0 ...250 V AC/DC)
- Approved for use in zone 2
Technical Specifications
Product properties
| MTTF | 889 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| MTTF | 391 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) |
| MTTF | 151 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) |
Insulation characteristics
| Overvoltage category | II |
| Degree of pollution | 2 |
Electrical properties
| Electrical isolation | 300 V (Rated insulation voltage (in each case between the digital inputs // digital outputs // TBUS supply, reinforced insulation in accordance with EN/IEC 61010)) |
| Electrical isolation | 50 V (Rated insulation voltage (in each case between the analog inputs / analog outputs / TBUS supply, reinforced insulation in accordance with EN/IEC 61010)) |
| Electrical isolation | 300 V (Rated insulation voltage (in each case between the digital inputs and outputs // analog inputs and outputs, reinforced insulation in accordance with EN/IEC 61010)) |
| Electrical isolation | 300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN/IEC 61010)) |
| Test voltage for digital I/Os | 2.5 kV AC (50 Hz, 1 min.) |
| Test voltage for analog I/Os | 1.5 kV AC (50 Hz, 1 min.) |
| Maximum power dissipation for nominal condition | 2.28 W |
| Transient surge protection | Yes |
Supply
| Supply Voltage Range | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
| Max. current consumption | ≤ 95 mA (At 24 V DC, at 25°C) |
Digital
| Max. current consumption | < 1 mA |
Analog
| Description of the input | Analog input |
| Number of Inputs | 1 |
| Current Input Signal | 0 mA ... 20 mA (can be set via DIP switches) |
| Current Input Signal | 4 mA ... 20 mA (can be set via DIP switches) |
| Max. current input signal | 22 mA |
| Input resistance current input | < 70 Ω |
| Resolution | 16 bit |
| Precision | ≤ 0.02 % (at 25 °C) |
| Protective circuit | Short-circuit and overload protection |
| Temperature coefficient, typical | typ. 0.0025 %/K (at -40 °C ... +70 °C) |
| Supply Voltage | 12 V DC (UANA via terminal block PWR1, +I1, for passive sensors, 25 mA) |
Digital
| Description of the input | Digital input |
| Number of Inputs | 2 |
| Voltage input signal | 0 V AC/DC ... 250 V AC/DC |
| Switching level "0" signal | 0 V AC/DC ... 4 V AC/DC (Low-voltage input) |
| Switching level "0" signal | 0 V AC/DC ... 20 V AC/DC (High-voltage input) |
| Switching level "1" signal | 10 V AC/DC ... 50 V AC/DC (Low-voltage input) |
| Switching level "1" signal | 50 V AC/DC ... 250 V AC/DC (High-voltage input) |
| Input Frequency | ≤ 2 Hz |
| Output name | Relay output |
| Number of Outputs | 2 |
| Contact switching type | Changeover contact |
| Contact Material | AgSnO2 |
| Maximum Switching Voltage | 250 V AC/DC |
| Min. switching current | ≥ 10 mA |
| Max. switching current | 2 A (250 V AC) |
| Max. switching current | 0.168 A (250 V DC) |
| Max. switching current | 2 A (24 V DC) |
| Mechanical service life | 1x 10⁷ cycles |
| Electrical service life | 2x 105 cycles (At 2 A, 250 V AC, cosφ 0.4) |
| Electrical service life | 2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms) |
| Maximum switching frequency | 2 Hz |
| Behavior of the outputs (adjustable via DIP switch) | Hold / Reset |
Analog
| Output name | Analog output |
| Number of Outputs | 1 |
| Voltage output signal | 0 V ... 10 V |
| Max. voltage output signal | ~ 10.83 V |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Max. current output signal | ~ 21.67 mA |
| Load | ≥ 10 kΩ |
| Load | ≤ 500 Ω |
| Resolution | 16 bit |
| Precision | ≤ 0.02 % (at 25 °C) |
| Precision | typ. 0.5 % (Voltage output) |
| Temperature coefficient, typical | typ. 0.0025 %/K (at -40 °C ... +70 °C) |
| Protective circuit | Transient protection of outputs |
Connection data
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Tightening torque | 5 lbf-in. ... 7 lbf-in. |
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Conductor cross section, rigid min. | 0.2 mm² |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
Signaling
| Status display | Green LED (supply voltage, PWR) |
| Status display | Green LED (bus communication, DAT) |
| Status display | Red LED (periphery error, ERR) |
| Status display | Yellow LED (digital input, DI1) |
| Status display | Yellow LED (digital input, DI2) |
| Status display | Yellow LED (digital output, DO1) |
| Status display | Yellow LED (digital output, DO2) |
Dimensions
| Width | 17.5 mm |
| Height | 113 mm |
| Depth | 114.5 mm |
Material specifications
| Color (Housing) | gray (RAL 7042) |
| Material (Housing) | PA 6.6-FR |
| Flammability rating according to UL 94 | V0 |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (>55°C derating, see technical documentation) |
| Ambient Temperature (Operation) | -40 °F ... 158 °F (>131°F derating, see technical documentation) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °F ... 185 °F |
| Altitude | 2000 m |
| Permissible humidity (operation) | 20 % ... 85 % |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
| Shock | 16g, 11 ms |
| Vibration (Operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
CE
| Certificate | CE-compliant |
UKCA
| Certificate | UKCA-compliant |
ATEX
| Identification | II 3 G Ex ec nC IIC T4 Gc |
| Certificate | IBExU 15 ATEX B008 X |
| Note | Please follow the special installation instructions in the documentation! |
IECEx
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | IECEx IBE 13.0019X |
EAC Ex
| Identification | 2Ex nA nC IIC T4 Gc X |
| Certificate | RU C-DE.HB49.B.00033/20 |
UL, USA/Canada
| Identification | 508 Listed |
| Identification | Class I, Div. 2, Groups A, B, C, D T4A |
| Identification | Class I, Zone 2, IIC T4 |
CCC / China-Ex
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | 2022122310115625 |
KC approval for South Korea
| Certificate | R-R-PCK-2901533 |
Corrosive gas test
| Identification | ISA-S71.04-1985 G3 Harsh Group A |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Standards and Regulations
| Standard designation | EMC Directive 2014/30/EU |
| Standards/specifications | EN 61000-6-2 |
| Standard designation | EMC Directive 2014/30/EU |
| Standards/specifications | EN 61000-6-4 |
| Standard designation | Ex Directive (ATEX) |
| Standards/specifications | EN 60079-0 |
| Standard designation | Ex Directive (ATEX) |
| Standards/specifications | EN 60079-15 |
Mounting
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2901533?
Proax is an authorized distributor of Phoenix Contact 2901533 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended